VAPOR CONTROL SYSTEMS
VAPOR CONTROL SYSTEMS
MODEL 1049
MODEL 5100
MODEL 5200
MODEL 7A00
MODEL 7A00
The Model 5200 is a low pressure/vacuum vent designed to vent the tank vapor away to a header system and to relieve vacuum pressure within the tank. The 5200 is a pilot operated design. The precision of the pilot feature allows tight seat leakage closer to set point and full flow with less overpressure.
The Model 1049 is a low pressure vent designed to vent the tank vapor away to header system, similar to the 5500. The 1049 is a pilot operated design. The precision of the pilot feature allows tight seat leakage closer to set point and full flow with less overpressure.
The Model 7A00 is an inline detonation flame arrestor. The primary function is to allow the flow of gases or vapor of flammable liquids through the enclosure, but prevent the transmission of a flame and suppress the effect of a detonation. The element inside the housing provides an extinguishing barrier to the ignited vapor mixture by absorbing heat from the flame. The element design is bi-directional and available for horizontal or vertical installations.
The Model 7A00 Detonator Pipe Fuse is a secondary protection system designed for use in potentially explosive atmospheres. The primary function is to prevent flame propagation in machinery or equipment containing flammable gas or vapor / air mixtures. The tape backup is a barrier to the burning flame by absorbing the heat.
The Model 5100is a low pressure/vacuum vent designed to vent the tank vapor away to atmosphere and to relieve vacuum pressure within the tank. The 5100 is a pilot operated design. The precision of the pilot feature allows tight seat leakage closer to set point and full flow with less overpressure.
Body Size:
Materials:
1049 Max. Pressure Setting: 14 psig, (0.96 barg)
2", 3", 4", 6", 8", 10", and 12"
CS Body/Pilot SST Body/Pilot
Body Sizes:
3/4", 1", 1-1/4", 1-1/2", 2", 2-1/2",3", 4", 5", 6", 8", 10", and 12"
Body Size:
5200 Max. Pressure Setting: 15 psig, (1 barg) 5200 Max. Vacuum Setting:
Body Size:
5100 Max. Pressure Setting: 15 psig, (1 barg) 5100 Max. Vacuum Setting:
2", 3", 4", 6", 8", 10", and 12"
MODEL 6A00
2", 3", 4", 6", 8", 10", and 12"
Connection:
Materials:
Materials:
Threaded version
CS Body with SST Bolt/Guides SST Body with SST Bolt/Guides Alum Body with SST Bolt/Guides
.5 psig, (0.03 barg) weight loaded and 15 psig spring package, (1 barg)
Materials:
CS Body/Hood with SST Bolt/Guides SST Body/Hood with SST Bolt/Guides Alum Body/Hood with SST Bolt/Guides
.5 psig, (0.03 barg) weight loaded and 15 psig, , (1 barg) spring package
The Model 6A00 is an inline deflagration flame arrestor. The primary function is to allow the flow of gases or vapor of flammable liquids through the enclosure, but prevent the transmission of a flame. The element inside the housing provides an extinguishing barrier to the ignited vapor mixture by absorbing heat from the flame. The element design is bi-directional and available for horizontal or vertical installations. MODEL 6E00 The Model 6E00 is an end of line deflagration flame arrestor. The primary function is to allow the flow of gases or vapor of flammable liquids through the enclosure.
CS or SST
Thread Sizes:
1/8 ", 1/4", 3/8 ", 1/2"
Element:
SST Material
MODEL 5500
MODEL 5400
Body Sizes:
Materials:
MODEL 7C00
The Model 5500 is a low pressure vent designed to vent the tank vapor away to a header system. The 5500 is a pilot operated design. The precision of the pilot feature allows tight seat leakage closer to set point and full flow with less overpressure.
3/4", 1", 1-1/4", 1-1/2", 2", 2-1/2", 3", 4", 5", 6", 8", 10", and 12"
CS or SST
The Model 5400 is a low pressure vent designed to vent the tank vapor away to atmosphere. The 5400 is a pilot operated design. The precision of the pilot feature allows tight seat leakage closer to set point and full flow with less overpressure.
Element:
The Model 7C00 unstable/overdriven detonation flame arrestor type II is a device that can be fitted to the opening of an enclosure or to the connecting pipe work of a system of enclosures. Its primary function is to allow the flow of gases or vapor of flammable liquids through the enclosure but prevent the transmission of a flame. The element inside the housing provides an extinguishing barrier to the ignited vapor mixture by absorbing heat from the flame. The Model 7C00 is used as an independent safety system to ensure explosion protection.
SST Material
Body Size:
Body Size:
2", 3", 4", 6", 8", 10", and 12"
2", 3", 4", 6", 8", 10", 12", 16", 18", 20", and 24"
Materials:
Materials:
CS Body with SST Bolt/Guides SST Body with SST Bolt/Guides Alum Body with SST Bolt/Guides 5500 Max. Pressure Setting: 15 psig, (1 barg)
CS Body/Hood with SST Bolt/Guides SST Body/Hood with SST Bolt/Guides Alum Body/Hood with SST Bolt/Guides
Body Sizes: 2", 3", 4", 6", 8", 10", and 12" Materials: CS or SST
Element:
Body Sizes:
Materials:
Element:
SST Material
3/4", 1", 1-1/4", 1-1/2", 2", 2-1/2", 3", 4", 5", 6", 8", 10", and 12"
CS or SST
SST Material
5400 Max. Pressure Setting: 15 psig, (1 barg)